[Features]●Does not use refrigerants such as freon. ●There is no driving part, and almost no maintenance is required. ●Compact and easy to install. ●The air that has been heat-exchanged inside the panel is automatically exhausted. ●The maximum ambient temperature for installation is 80°C. ●Can be used in dusty environments.
[Use] ●To prevent troubles with control panels and electronic devices. ●For cooling control panels, industrial cameras, and sensor boxes.
[Specifications] ● Air consumption (L/min): 105 to 224 ● Connection diameter: NPT-1/8 ● Compressed air supply port: NPT-1/8 ● Maximum working pressure (MPa): 1.0 ● Working air pressure ( MPa): 0.27 to 0.69 Working pressure (MPa): 0.27 to 0.69 Total length (mm): 181 Applicable fluid: Compressed air (compressor air)
[Specification 2] ● Applicable fluid: Compressed air (air) ● Air consumption (NL/min) 105 to 224: 0.27 MPa to 069 MPa ● Cooling capacity (w) 54 to 115: 0.27 MPa to 069 MPa ● Continuous cool air discharge type ● With vinyl hose for internal piping Working air pressure (MPa): 0.27 to 0.69